Cyrix-Li-charge 12/24V-120A intelligent charge relay
The Cyrix-Li-Charge connects a battery charger with a 3-second delay under specific voltage conditions and reengages after disengaging due to overvoltage or low battery voltage.
- The Cyrix-Li-Charge disengages immediately if its control input becomes free floating, signaling cell overvoltage or overtemperature.
- After two failed reengagement attempts, the delay increases to 10 minutes.
- The device disengages with a 1-hour delay when battery voltage drops below 13.5 V.